FINAL DRAFT 2-29-96
Revised 10/96
Design Standards
Megavoltage Unit
ARCHITECTURAL
POWER
Ceiling:
General:
Ceiling Ht:
2895 mm (9'-6")
Emergency:
--
Wall Finish:
Notes: 1. 480V, 3P flush mounted circuit
Painted
breaker with shunt trip for linear
Wainscot:
--
accelerator system. Coordinate
Base:
Resilient base
rating with system supplier.
2. Emergency power off (EPO) push
Slab Depr:
Coordinate with equipment
button station. Connect to shunt trip
manufacturer
circuit breaker.
Notes:
1200mm (4'-0") wide automatic
COMMUNICATION
door. See VA Construction
Standard 64-1, X-Ray
ADP:
--
Radio:
--
Control".
Telephone:
Yes
Intercom:
Yes
SPECIAL EQUIPMENT
Public Addr:
Yes
Notes: 1. Junction box for CCTV camera with
None
conduit to control room.
LIGHTING
2. Junction box for CCTV monitor
cabling.
General:
Control Rm:
0-30fc=1.3w/sf
Megavoltage Rm: 0-30fc=2.6w/sf
Special:
--
Notes:
1. "Beam On" and "Beam Ready"
warning sign fixture.
2. Continuous fluorescent
direct/indirect fixture, acrylic
prismatic lens on top and bottom,
with 2-F32T8 lamps, 4100 deg. K
CRI=85.
3. 600mm x 1200mm (2'x4')
recessed fluorescent light
fixtures, acrylic prismatic lens,
w/2-F32T8 lamps, 4100 deg. K,
CRI-85 (minimum).
4. 600mm x 600mm (2'x2')
acrylic prismatic lens, w/2 FB31
lamps, 4100 deg. K, CRI-85
downlight with 100W, A-21 lamp
VA DESIGN GUIDE
GUIDE PLATE 4-5