FINAL DRAFT 9-26-95
REVISED FEBRUARY 1997
Sleep Study Suite/Diagnostic Room
Design Standards
ARCHITECTURAL
Ceiling:
Acoustical ceiling tile
ADP:
Yes
Ceiling Ht:
2700 mm (9'-0")
Radio:
---
Wall Finish:
Paint
Telephone:
Yes
Wainscot:
---
Intercom:
Yes
Base:
Resilient Base
Public Addr:
---
Notes:
1.Junction box for CCTV
Floor Finish:
system with conduit from
Slab Depr:
---
adjacent patient bedroom
2.Junction box for
Notes:
---
polysomnograph cabling
with conduit from adjacent
patient bedroom.
SPECIAL EQUIPMENT
None
CONDITIONING
Dry Bulb Temp Cooling: 24 deg C (76 deg F)
ELECTRICAL
Dry Bulb Temp Heating: 25 deg C (78 deg F)
General:
30 FC
Minimum % Outside Air:
15%
Notes:
1. 600 mm x 1200 mm
---
fluorescent light
Noise Criteria:
NC-35
fixtures, acrylic
prismatic lens, W/2-
Steam:
---
F32T8 lamps, 3500k,
Relative Humidity/Cooling:
50%
CRI=75 (minimum).
Relative Humidity/Heating:
30%
POWER
Minimum Air Changes/Hr.:
4
General:
Room Pressure:
0
Emergency:
500 W (crash cart receptacle)
AC Load-Equipment:
75 W/sm (7 W/sf)
Notes:
---
AC Load-Lighting:
22 W/sm (2 W/sf)
Number of People:
3
---
Notes:
---
VA DESIGN GUIDE
PULMONARY MEDICINE SERVICE
PLATE 5-6