FINAL DRAFT 9-26-95
REVISED FEBRUARY 1997
Viewing Room/Library/AV Studies
Design Standards
ARCHITECTURAL
Ceiling:
Acoustical ceiling tile
ADP:
Yes
Ceiling Ht:
2700 mm (9'-0")
Radio:
---
Wall Finish:
Vinyl wall covering
Telephone:
Yes
Wainscot:
---
Intercom:
---
Base:
Resilient Base
Public Addr:
Yes
Floor Finish:
Carpet
Notes:
---
Slab Depr:
---
Notes:
1. 900 mm (3"-0") wide door
with tempered glass view
CONDITIONING
window.
0
C(780 F)
Dry Bulb Temp Cooling:
25
2. See
VA
construction
standard
34-1,
"Noise
0
0
22 C (72 F)
Transmission Control".
Minimum % Outside Air:
15%
SPECIAL EQUIPMENT
---
None
Noise Criteria:
NC-35
Steam:
---
ELECTRICAL
Relative Humidity/Cooling:
50%
General:
30 FC
Relative Humidity/Heating:
30%
Notes:
1. 600 mm x 1200 mm (2' x
Minimum Air Changes/Hr.:
4
light
fixtures,
acrylic
Room Pressure:
0
prismatic lens, W/2-F32T8
AC Load-Equipment:
75 W/sm (7 W/sf)
lamps, 3500k, CRI=75
(minimum)
AC Load-Lighting:
11 W/sm (1 W/sf)
Number of People:
6
POWER
---
General:
Notes:
---
Emergency:
---
Notes:
---
VA DESIGN GUIDE
PULMONARY MEDICINE SERVICE
PLATE 4-1