Final Draft 11-30-95
Revised March 1997
Design Standards
ARCHITECTURAL
CONDITIONING
Ceiling:
Ceiling Ht:
2740 mm (9'-0")
Dry Bulb Temp Cooling:
22C (72F)
Wall Finish:
Paint
22C (72F)
Wainscot:
--
Minimum % Outside Air:
--
Base: Integral welded seam sheet flooring base
Yes
Floor Finish:
Welded seam sheet flooring
Noise Criteria:
NC-40
Slab Depr:
--
Steam:
--
Notes:
1. 1060mm (3'-6") Wide Door
Relative Humidity/Cooling:
50%
Relative Humidity/Heating:
30%
SPECIAL EQUIPMENT
Minimum Air Changes/Hr.:
12 (Prep Area)
Room Pressure:
Negative for Prep Area
None
Equal for reference area
LIGHTING
with respect to corridor
AC Load Lighting: 22 w/sm (2 w/sf) both rooms
General:
70 FC
AC Load Equipment:
194 w/sm (18 w/sf)
Special:
--
Number of People:
4 per room
Notes:
Special Exhaust:
fluorescent light fixture, acrylic
system for Laminar Flow
prismatic lens, W/2-F32T8 lamps,
H12-B2 hood. See HVAC Design
4100 K CRI=85 (minimum)
Manual for Hospital Projects.
2. 300mm x 1300mm (1'x4")
Notes:
--
acrylic prismatic lens, W/1-F32T8
lamps, 4100 K
PLUMBING AND MEDICAL GASES
Cold Water:
--
Hot Water:
--
POWER
Laboratory Air:
--
General:
Laboratory Vacuum:
--
Emergency:
Sanitary Drain:
--
Notes:
1. Junction box for Laminar Flow
Reagent Grade Water:
--
Hood on emergency power.
Medical Air:
--
Medical Vacuum:
--
Oxygen:
--
ADP:
Yes
Notes:
--
Radio:
--
Telephone:
Yes
Intercom:
Yes
Pub. Addr:
--
Notes:
--
VA DESIGN GUIDE
PHARMACY SERVICE
PAGE 4 - 7