First Draft 8-14-96
Revised June 97
Design Standards
Drug Information Service
ARCHITECTURAL
CONDITIONING
Ceiling:
Ceiling Ht:
2740 MM (9'-0")
Dry Bulb Temp Cooling:
25C (78F)
Wall Finish:
Painted Gypsum Wallboard
22C (72F)
Wainscot:
--
Minimum % Outside Air:
15
Base:
Resilient base
--
Floor Finish:
Noise Criteria:
NC-35
Slab Depr:
--
Steam:
--
Notes:
--
Relative Humidity/Cooling:
50%
Relative Humidity/Heating:
30%
SPECIAL EQUIPMENT
Minimum Air Changes/Hr.:
4
Room Pressure:
0
None
AC Load Lighting:
18 w/sm (1.7 w/sf)
AC Load-Equipment:
43 w/hr (4 w/hr)
LIGHTING
Number of People:
3
General:
1.7 w/sf538 lx (50 FC)
--
Special:
--
Notes:
--
Notes:
1. Dual-level switching provided
50/15 FC levels.
PLUMBING AND MEDICAL GASES
Cold Water:
--
fluorescent light fixture, parabolic
Hot Water:
--
louver lens, W/3-F32T8 lamps,
Laboratory Air:
--
3500K, CRI=75 (Minimum)
Laboratory Vacuum:
--
Sanitary Drain:
--
POWER
Reagent Grade Water:
--
Medical Air:
--
General:
Medical Vacuum:
--
Emergency:
--
Oxygen:
--
Notes:
Notes:
COMMUNICATION
ADP:
Yes
Radio:
--
Telephone:
Yes
Intercom:
--
Pub. Addr:
--
Notes:
--
VA DESIGN PRIMER
OUTPATIENT PHARMACY
PAGE 4-1