June 99
openings, and platforms for access to HVAC
equipment and supports for mechanical equipment.
C. Electrical drawings and specifications provide motor
starters and disconnectors, not furnished as part of
HVAC equipment, smoke detectors (duct and/or space
mounted), all power wiring to HVAC smoke dampers,
motors, heating cable, and controls for winterizing
piping.
D. Plumbing drawings and specifications provide all floor
drain outlets.
2.
BASIC DESIGN PARAMETERS:
2.1
INDOOR DESIGN CONDITIONS: (Degrees C (F) dry bulb
and percent relative humidity)
TABLE 2.1
ROOM or AREA
SUMMER
WINTER
Db.
%RH
Db.
Multipurpose Room
25 (78)
55
22(72)
---------------------------------------
Offices, Operational Center
25 (78)
55
22 (72)
---------------------------------------
Lunch Room
25 (78)
55
22 (72)
---------------------------------------
Reception
25 (78)
55
22 (72)
---------------------------------------
Maintenance Shops
(No Mech. Cooling)
20 (68)
---------------------------------------
Equipment Storage Area
(No Mech. Cooling)
---------------------------------------
Toilets, Locker Room
25 (78)
55
22 (72)
---------------------------------------
H.A.C.
25 (78)
55
22 (72)
---------------------------------------
Electrical Closets
(See Note Below)
---------------------------------------
Telephone Closets
(See Notes Below)
---------------------------------------
Flammable Storage
---------------------------------------
Pesticide Storage
NOTES ON INDOOR DESIGN CONDITIONS:
VA Design Guide -- National Cemetery Administration
Page 5 -53