JULY 2005
Design Standards
Toilet, Wheelchair Accessible
HEATING, VENTILATING AND AIR
ARCHITECTURAL
CONDITIONING
Coordinate with SFO; refer to Template SFO
Coordinate with SFO; refer to Template SFO
Section 7, and Schedule C.
Section 6.5.
Ceiling:
AT
Dry Bulb Temp Cooling: Indirect by transfer (see
Ceiling Height:
2740 mm (9'-0")
note)
Wall Finish:
Painted GWB
Dry Bulb Temp Heating: Indirect by transfer (see
Wainscot:
CT
note)
Base:
CT
Minimum % Outside Air:
Floor Finish:
CT
Yes
Slab Depression:
--
Noise Criteria:
NC-40
Sound Protection:
STC 40
Steam:
--
Notes:
--
Relative Humidity/Cooling:
Relative Humidity/Heating:
LIGHTING
Minimum Air Changes/Hr.: 10
Room Pressure:
Negative
Coordinate with SFO; refer to Template SFO
AC Load-Equipment:
Section 6.7, 6.7.1, 6.7.5.
AC Load-Lighting:
General:
30 FC
Number of People:
1
Special:
--
--
Notes:
--
Note: Exterior toilets:
Heating and cooling
required cooling DB 25 (78F) and heating
POWER
22C (72F)
--
Coordinate with SFO; refer to Template SFO
Section 6.7, 6.7.1, 6.7.3, 6.7.4 and Schedule B.
PLUMBING AND MEDICAL GASES
General:
Yes
Coordinate with SFO; refer to Template SFO
Emergency:
--
Section 6.6 and Schedule B
Notes:
--
Cold Water:
Yes
Hot Water:
Yes
COMMUNICATION/SPECIAL SYSTEMS
Laboratory Air:
--
Laboratory Vacuum:
--
Coordinate with SFO; refer to Template SFO
Sanitary Drain:
Yes
Sections 6.7.8, 6.7.9, and Schedule B.
Reagent grade Water:
--
Data:
--
Medical Air:
--
Telephone:
--
Medical Vacuum:
--
Intercom:
--
Oxygen:
--
Nurse Call:
Yes
Notes:
--
Public Address:
--
Radio/Entertainment: --
MATV:
--
CCTV:
--
MID:
--
Security/Duress:
--
VTEL:
--
VA Satellite TV:
--
Notes:
--
VA DESIGN GUIDE
APPENDIX B
LEASE BASED OUTPATIENT CLINICS
2-21.3