JULY 2005
Design Standards
Radiology Film Viewing
4. Outlet, TV monitor (x-ray
ARCHITECTURAL
TV chain)
Coordinate with SFO; refer to Template SFO
Section 7, and Schedule C.
COMMUNICATION/SPECIAL SYSTEMS
Ceiling:
AT
Coordinate with SFO; refer to Template SFO
Ceiling Height:
2740 mm (9'-0")
Sections 6.7.8, 6.7.9, and Schedule B.
Wall Finish:
Painted GWB
Data:
Yes
Wainscot:
--
Telephone:
Yes
Base:
Resilient Base
Intercom:
--
Floor Finish:
Carpet
Nurse Call:
--
Slab Depression:
--
Public Address:
--
Sound Protection:
--
Radio/Entertainment: --
Notes:
1 hour fire rated con-
MATV:
--
struction around film
CCTV:
Yes
library. Coordinate floor
MID:
--
loading requirement in
Security/Duress:
--
film library with struc-
VTEL:
--
tural engineer.
VA Satellite TV:
--
Notes:
--
LIGHTING
Coordinate with SFO; refer to Template SFO
HEATING, VENTILATING AND AIR
Section 6.7, 6.7.1, 6.7.5.
CONDITIONING
General:
20 FC Common
Coordinate with SFO; refer to Template SFO
Viewing Room
Section 6.5.
20 FC Multi-Viewing Area
26C (78F)
Dry Bulb Temp Cooling:
Special:
--
22C (72F)
Notes:
2' X 4' fluorescent
Minimum % Outside Air:
15%
--
acrylic prismatic lens
Noise Criteria:
NC-40
Steam:
--
POWER
Relative Humidity/Cooling: 50%
Coordinate with SFO; refer to Template SFO
Section 6.7, 6.7.1, 6.7l.3, 6.7.4 and Schedule B.
Minimum Air Changes/Hr.: 4
General:
Yes
Room Pressure:
0
Emergency:
--
AC Load-Equipment:
4 W/SF
Notes:
When a Conference Room
AC Load-Lighting:
1.6 W/SF
is not provided to the Radi-
Number of People:
10
ology Common Viewing
--
Room, add the following to
Notes:
--
this room:
1. Outlet, camera, closed
PLUMBING AND MEDICAL GASES
circuit television (empty
Coordinate with SFO; refer to Template SFO
conduit system) (PG-
Section 6.6 and Schedule B
18-1, MCS 16111)
Cold Water:
--
2. Outlet, monitor, closed
Hot Water:
--
circuit television, 457 mm
Laboratory Air:
--
(18") above finished floor
Laboratory Vacuum:
--
(empty conduit system)
Sanitary Drain:
--
(PG-18-1, MCS 16111)
Reagent grade Water:
--
3. Outlet, projector, film, x-
Medical Air:
--
ray (PG-18-1, MCS
Medical Vacuum:
--
16140)
Oxygen:
--
Notes:
--
VA DESIGN GUIDE
APPENDIX B
LEASE BASED OUTPATIENT CLINICS
2-17.3