JULY 2005
Design Standards
Pharmacy, Expanded Service
ARCHITECTURAL
CONDITIONING
Coordinate with SFO; refer to Template SFO
Coordinate with SFO; refer to Template SFO
Section 7, and Schedule C.
Section 6.5.
Ceiling:
AT
22C (72F)
Dry Bulb Temp Cooling:
Ceiling Height:
2740 mm (9'-0")
22C (72F)
Wall Finish:
Painted GWB
Minimum % Outside Air:
15%
Wainscot:
--
--
Base:
Resilient Base
Noise Criteria:
NC-40
Floor Finish:
Carpet
Steam:
--
Slab Depression:
--
Relative Humidity/Cooling:
50%
Sound Protection:
--
Relative Humidity/Heating:
30%
Notes:
Physical Security; see
Minimum Air Changes/Hr.:
6
4.2.7 in Template SFO
Room Pressure:
Positive
LIGHTING
AC Load-Equipment:
2.0 W/SF
AC Load-Lighting:
1.6 W/SF
Coordinate with SFO; refer to Template SFO
Number of People:
4
Section 6.7, 6.7.1, 6.7.5.
--
General:
Yes
Notes:
--
Special:
--
Notes:
Emergency critical
PLUMBING AND MEDICAL GASES
power source
Coordinate with SFO; refer to Template SFO
POWER
Section 6.6 and Schedule B
Coordinate with SFO; refer to Template SFO
Cold Water:
Yes
Section 6.7, 6.7.1, 6.7.3, 6.7.4 and Schedule B.
Hot Water:
Yes
General:
Yes
Laboratory Air:
--
Emergency:
Yes
Laboratory Vacuum:
--
Notes:
Sanitary Drain:
Yes
erator on emergency
Reagent grade Water:
--
critical source.
Medical Air:
--
2. Roll down grille at
Medical Vacuum:
--
waiting may be
Oxygen:
--
motorized.
Notes:
--
COMMUNICATION/SPECIAL SYSTEMS
Coordinate with SFO; refer to Template SFO
Sections 6.7.8, 6.7.9, and Schedule B.
Data:
Yes
Telephone:
Yes
Intercom:
--
Nurse Call:
--
Public Address:
--
Radio/Entertainment: --
MATV:
--
CCTV:
--
MID:
--
Security/Duress:
Yes
VTEL:
--
VA Satellite TV:
--
Notes:
--
VA DESIGN GUIDE
APPENDIX B
LEASE BASED OUTPATIENT CLINICS
2-12.3