September 30, 1995
Design Standards
Confocal Microscope Room
ARCHITECTURAL
Floor Area
14 m (147 ft)
Wall Finish
gwb
Ceiling
at
Base
rb
Ceiling Height
2700 mm (9 ft)
Floor Finish
vct
RFI Shielding
-
Slab Depression
-
Soundproofing
-
Floor Load
-
Lighting
ELECTRICAL
Power
General
325 lx (30 fc)
General
-
Special
-
Special
-
Incandescent fixtures with PAR38 halogen flood lamps on
Emergency
-
dimmer switch
Telephone
yes
ADP
yes
HEATING, VENTILATING AND AIR CONDITIONING
AC Load Lights
600 W
Dry Bulb Temp Cooling
24C (76F)
AC Load Equipment
48 W/m (4.5 W/ft)*
22C (72F)
Number of People
3
Relative Humidity - Cooling
50%
Noise Criteria
NC-40
Relative Humidity - Heating
30%
Room Pressure
positive
Minimum % Outside Air
100
Min Air Changes per Hour 6
yes
Steam
-
-
*Based on water cooled laser generator. See note 1 below.
PLUMBING AND LABORATORY GASES
Sanitary Drain
-
Cold Water
see below
Acid Waste
-
Hot Water
-
Other
-
Reagent Grade Water
-
Fuel Gas
-
Laboratory Air
-
-
Laboratory Vacuum
-
Additional Notes:
1.
Use of water-cooled laser generators is preferred as air-cooled generators dissipate excessive heat into the
room. Tie into a common closed circuit cooler for all water-cooled equipment in the Research Facility. Provide
domestic water backup for cooling water in case of emergency.
Guide Plate 5-4
VA Design Guide -- Research Laboratory