First Draft 6-28-97
Design Standards
Pretesting, Fitting & Dispensing Room and
Consultation/Viewing Room
ARCHITECTURAL
CONDITIONING
Ceiling:
Gypsum wallboard lay-in ceiling panels
Ceiling Ht:
2400 mm (8'-0")
Dry Bulb Temp Cooling:
25C (78F)
Wall Finish:
Paint
22C (72F)
Wainscot:
--
Minimum % Outside Air:
25%
Base:
Resilient base
--
Floor Finish:
Noise Criteria:
NC-40
Slab Depr:
--
Steam:
--
Notes:
--
Relative Humidity/Cooling:
50%
Relative Humidity/Heating:
30%
SPECIAL EQUIPMENT
Minimum Air Changes/Hr.:
4
2
30 W/m (2.8 W/sf)
AC Load Lighting:
None
2
19 W/m (1.76 W/sf)
AC Load-Equipment:
Number of People:
2 each room
LIGHTING
--
General:
50 FC (1.4 W/sf) - Ambient
Notes:
--
100 FC (/2.8 W/sf) - Task
Special:
--
PLUMBING AND MEDICAL GASES
Notes:
1. 600 mm x 1200 mm (2'x4')
Cold Water:
Yes
Hot Water:
Yes
acrylic prismatic lens on top and
Laboratory Air:
--
bottom, W/4-F32T8 lamps, 4100
Laboratory Vacuum:
--
deg. K, CRI=85 (min.)
Sanitary Drain:
Yes
Reagent Grade Water:
--
POWER
Medical Air:
--
General:
Medical Vacuum:
--
Emergency:
--
Oxygen:
--
Notes:
--
Notes:
--
COMMUNICATION
ADP:
Yes
Radio:
--
Telephone:
Yes
Intercom:
--
Pub. Addr:
--
Notes:
--
VA DESIGN GUIDE
EYE CLINIC
PAGE 4-4