First Draft 6-28-97
Design Standards
Examination/Treatment Room
ARCHITECTURAL
CONDITIONING
Ceiling:
Gypsum wallboard lay-in ceiling panels
Ceiling Ht:
2400 mm (8'-0")
Dry Bulb Temp Cooling:
25C (78F)
Wall Finish:
Paint
22C (72F)
Wainscot:
--
Minimum % Outside Air:
25
Base:
Resilient base
--
Floor Finish:
Noise Criteria:
NC-40
Slab Depr:
--
Steam:
--
Notes:
--
Relative Humidity/Cooling:
50%
Relative Humidity/Heating:
30%
SPECIAL EQUIPMENT
Minimum Air Changes/Hr.:
4
Room Pressure:
0
None
2
30 W/m ( 4 W/sf)
AC Load Lighting:
2
65 W/m (6 W/sf)
AC Load-Equipment:
LIGHTING
Number of People:
3
General:
50 FC (1.4 W/sf) - Ambient
--
100 FC (/2.8 W/sf) - Task
Notes:
--
Special:
--
Notes:
1. Provide dimmer controls for
PLUMBING AND MEDICAL GASES
Opthamolic stands.
Cold Water:
Yes
2. 600 mm x 1200 mm (2' x 4')
Hot Water:
Yes
Laboratory Air:
--
acrylic prismatic lens, W/4-F32T8
Laboratory Vacuum:
--
lamps, 4100 deg. K, CRI=8.5
Sanitary Drain:
Yes
(min.)
Reagent Grade Water:
--
Medical Air:
--
POWER
Medical Vacuum:
--
Oxygen:
--
General:
Notes:
--
Emergency:
--
Notes
--
COMMUNICATION
ADP:
Yes
Radio:
--
Telephone:
Yes
Intercom:
--
Pub. Addr:
--
Notes:
--
VA DESIGN GUIDE
EYE CLINIC
PAGE 4-2