EQUIPMENT GUIDE LIST - CHAPTER 277
07-02
RADIATION THERAPY SERVICE
SYMBOL
QNTY
ACQ/INS
DESCRIPTION
SPEC
REFERENCE
DETAIL
OUTLETS, RADIATION THERAPY PLANNING COMPUTER SYSTEM
(EMPTY CONDUIT SYSTEM) (SEE ELECTRICAL ENGINEERING
AR
CC
SERVICE GUIDE LINES)
1
VV
CHAIR, ROTARY, WITH ARMS
TABLE, LIGHT, 120 VOLT, 20 AMP, APPROX., 610 mm X 914 mm, 762
1
VV
mm X 1067 mm (24" X 36", 30" X 42")
CABINET, WALL, WITH SLOPING TOP, 2 GLAZED SLIDING DOORS
AND 2 ADJUSTABLE SHELVES, AVAILABLE WIDTHS - 762 mm, 914
mm, 1067 mm, 1219 mm (30", 36", 42", 48"); DEPTH - 330 mm (13");
VL25
1
CF
HEIGHT - 762 mm (30")
TREATMENT AREA:
NOTE: THE FOLLOWING X-RAY EQUIPMENT TO BE DETERMINED ON
PROJECT BASIS BY VETERANS HEALTH ADMINISTRATION.
1
VC
1
VC
POWER UNIT DEVICE
2
VC
COOLER, WATER
1
VC
STABILIZER
INSTALL POWER UNIT DEVICE, WATER CO0LER AND STABILIZER IN
AN ENCLOSED SPACE NOT LESS THAN, 1524 mm X 3048 mm (5'- 0" X
10'- 0") WITH VENTILATION TO DISSIPATE HEAT GENERATED,
AMOUNT OF EQUIPMENT VARIES WITH MANUFACTURER.
NOTE: SERVICES, ELECTRICAL & PLUMBING, AS REQUIRED FOR
EQUIPMENT.
1
VV
TABLE, THERAPY, HYDRAULIC, MOBILE
DOOR, POWER OPERATED, WITH ELECTRIC SAFETY INTERLOCK
1
CC
TIED INTO CONTROL PANEL WITH LEAD GLASS WINDOW
08721
1
CC
WINDOW, VIEWING, LEAD GLASS, FOR PATIENT OBSERVATION
13091
13091-1.DWG,
SHIELDING, RADIATION, FOR ROOMS WITH FIXED X-RAY EQUIPMENT,
08110-3.DWG,
AR
CC
IN ACCORDANCE WITH (NCRP REPORT NO. 33, 35 AND 49)
13091
ARCH DM
& 13091-2.DWG
SPEAKER, WITH CHANNEL SELECTOR AND VOLUME CONTROL,
1
CC
HOSPITAL RADIO SYSTEM
16771
LOW LEVEL DIMMED INCANDESCENT LIGHTING SYSTEM IN ADDITION
AR
CC
16510
CONTROL AREA:
Page 14