EQUIPMENT GUIDE LIST - CHAPTER 275
07-02
SYMBOL
QNTY
ACQ/INS
DESCRIPTION
SPEC
REFERENCE
DETAIL
1
VV
DISPENSER, SOAP, LIQUID, WALL MOUNTED
1
CC
DISPENSER, PAPER TOWEL AND DISPOSAL COMBINATION UNITS
10800
1
VV
DISPENSER, SANITARY NAPKIN
1
VV
DISPOSAL, SANITARY NAPKIN
1
VV
RECEPTACLE, WASTE, 330 mm (13") DIAMETER
STATION, CALL, EMERGENCY, WITH SIGNAL OVER DOOR AND LIGHT
1
CC
AND SOUND SIGNAL IN WORK AREA
16761
AR
VC
GANTRY, MAGNET, PATIENT COUCH, SIZE AS REQUIRED
AR
VC
RADIO FREQUENCY COPPER GROUND PLANES, LOCATED ON THE
FINISHED FLOOR SURFACE, FROM THE MAGNET TO THE
AR
VC
ELECTRONIC CABINETS
AR
VC
SHIELDING, MAGNETIC (ACTIVE OR PASSIVE)
AR
CC
COMPUTER/ACCESS FLOORING, NON-MAGNETIC MATERIAL
AR
CC
INTERCOM, STATION, NON-MAGNETIC MATERIAL
16760
AR
CC
OUTLET, INTERCOM (EMPTY CONDUIT SYSTEM)
16111
NOTE: INTERCOM STATION CONNECTED TO STATION IN THE
CONTROL ROOM.
LIGHTING SYSTEM, DC, FOR INCANDESCENT LIGHT FIXTURES, NON-
AR
CC
MAGNETIC MATERIAL, MULTI-CIRCUIT LIGHT FIXTURES
CONNECTIONS, PLUMBING, ELECTRICAL OR MECHANICAL AS
AR
CC
REQUIRED
NOTE: CONDUCTIVE CONNECTIONS ARE TO BE MADE OUTSIDE THE
RF ROOM.
SYSTEM EMERGENCY OFF BUTTON PANEL, GUARD COLLAR, FLUSH
MOUNTED, LOCATED NEAR EXIT FROM GANTRY ROOM, APPROX.,
1
VC
1524 mm (60") ABOVE FINISHED FLOOR
OXYGEN MONITOR AND ALARM, WALL MOUNTED, APPROX., 279 mm
X 178 mm X 229 mm (11" X 7" X 9") LOCATED APPROX., 1524 mm (60")
1
VC
ABOVE FINISHED FLOOR
NOTE: PROVIDE NON-MAGNETIC MATERIAL FOR AIR, OXYGEN AND
VACUUM OUTLETS FROM PORTABLE SUPPLY, ONLY WHEN
APPROVED FOR A SPECIFIC PROJECT BY VHA.
Page 7