All Future Floors (Unless Otherwise Noted)
(60)**
300
Administrative Services
(80)
400
Bed Rooms
(40)
200
Corridors
(60)
300
Loading Docks and Platforms
(250)
1200
Lobbies
(100)
500
Mechanical Rooms
(150)
750
Pharmacy
(100)
500
Recreation and Dining Areas
(100)
500
Footnotes:
*
Design Live Loads shall be noted on the drawings in general notes and
on plans to indicate specific areas designed for different loads.
Column design loads shall be noted in column schedules.
** All non-bed areas of future floors shall be designed for a live load
of 500 kg/m2 100 (psf).
2