01-06M
See Master Specification 15200 for base and isolator description. Minimum
deflection indicated as millimeters.
Equipment
Equipment Location
On Grade
6 m (20 ft.)
9 m (30 ft.)
Floor Span
Floor Span
Base
Isol
Min.
Base
Isol
Min.
Base
Isol
Min.
Type
Type
Defl
Type
Type
Defl
Type
Type
Defl
PUMPS
Close Coupled
Up to 1200 w
--
--
--
--
D, L,
--
--
D, L,
--
W
W
Over 1200 w
--
--
--
I
S
25
I
S
25
Base Mounted
Up to 7500 w
--
--
--
--
D, L,
--
--
D, L,
--
W
W
EQUIPMENT
EQUIPMENT LOCATION
12 m (40 ft.)
15 m (50 ft.)
Floor Span
Floor Span
Base
Isol
Min.
Base
Isol
Min.
Type
Type
Defl
Type
Type
Defl
PUMPS
Close Coupled
Up to 1200 W
--
D, L, W
--
--
D, L, W
--
Over 1200 W
I
S
43
I
S
43
Base Mounted
Up to 7500 W
--
D, L, W
--
--
D, L, W
--
Notes:
1.
For suspended floors lighter than 102 mm (4") concrete, select
deflection requirement from next higher span.
2.
If equipment is located in a building separated from building housing
patients, isolator pads are not required.
3.
Provide pads (D) for domestic water booster pump package.
4.
This chart applies to non-seismic areas. If in VA Seismic Area A or B,
substitute DS for D, and SS for S.
5.
SI Conversion: 25 mm = 1", 43 mm = 1.7", 1200 W = 1-1/2 HP, and 7500 W
= 10 HP.
14