B.
Piping Plans and Sections: Show the locations of required
restraints with reference to SMACNA, NUSIG, or special
restraint details, whichever is applicable.
C.
Equipment Restraints: Show special details where required.
Pay particular attention to suspended equipment.
13.
SUBMISSIONS:
13.1
Submit calculations required under the Contract to include the
following systems and equipment:
Soil, Waste and Vent
Water Heater
Storm Drainage
Domestic Water
Pumps
Fuel Gas
Vacuum
13.2
Recommendation regarding the necessity for installing insulation
on the domestic water and horizontal storm drainage piping for the
13.3
Water analysis, including pH, total hardness as CaCO3, total
dissolved solids, and alkalinity.
PLUMBING FIXTURE SCHEDULES: Use the following data for design of water
14.
the reference plumbing code. Plumbing fixtures are described in Master
Specification 15450, PLUMBING FIXTURES.
14.1
FIXTURE UNITS:
P-NUMBER
DESCRIPTION
DRAIN
SUPPLY
CW
HW
TOTAL
103
Water Closet, Flush Valve
6
6
-
6
201-202
Urinal, Siphon Jet
4
5
-
6
401, 415, 418
Lavatory
1
.6
.6
.8
502
Service Sink
3
2.25
2.25
3
604
Electric Water Cooler
.5
.5
-
.5
702
Shower
2
1.5
1.5
2
706
Emergency Shower
-
-
-
-
707, 712
Emerg. Shower, Eye & Face
-
-
-
-
Wash
708
Emerg. Eye & Face Wash
-
-
-
-
801
Wall Hydrant
-
-
-
-
802
Hose Bibb
-
-
-
-
14.2
MINIMUM FIXTURE BRANCH SIZES (mm):
P-NUMBER
DESCRIPTION
DRAINAGE
SUPPLY
WP
VP
CW
HW
103
Water Closet, Flush Valve
100
50
25
-
201-202
Urinal, Siphon Jet
50
50
20
-
6