06-06
B. NUSIG manuals of designs are pre-calculated from 0.05 g through 1.00
g in increments of 0.05 g.
8.4 CALCULATIONS
Unless otherwise shown by SMACNA or NUSIG, provide detailed structural
calculations for VA's review on design of hangers, supports, anchor
bolts, and connections. Show sizes, spacing, and length for securing
to structural members, and length and sizes of welds anchored to steel
members.
8.5 DRAWINGS
A. Where SMACNA or NUSIG details are incomplete or not applicable, show
complete seismic restrain requirements and coordinate with the
specifications. Coordinate mechanical work with architectural and
structural work. Special provisions and details may be required.
B. Ductwork and Piping Plans and Sections: Show the locations of
required restraints with reference to SMACNA, NUSIG, or special
restraint details, whichever is applicable.
C. Equipment Restraints: Show special details where required. Pay
particular attention to suspended equipment.
31