return room air back to the air-handling unit when the hood is not in
operation.
4.3 ELEVATOR MACHINE ROOMS
See Article 2.10.5
See Article 2.10.6
4.5 FLAMMABLE AND COMBUSTIBLE LIQUID STORAGE SPACES
4.5.1 GENERAL
The mechanical ventilation system shall be designed in accordance with
NFPA-30.
4.5.2 HVAC REQUIREMENTS
(a) Each flammable and combustible liquids storage space shall have its
own dedicated exhaust system. The exhaust fan shall discharge at a safe
distance above the highest point of the building to prevent
recirculation.
(b) Exhaust air at the rate of 0.27 Cu M/Sq M (1.0 CFM/Sq. Ft) with a
minimum of 4.5 Cu M/Min (150 CFM).
(c) Exhaust fan shall be on emergency power.
(d) Locate the exhaust and make-up air inlets 300 mm (12 inches) above
the finished floor on the opposite side of room to avoid short-
circuiting of air.
(e) Provide an explosion proof motor and spark-proof fan. The fan
bearings should not come in contact with the exhaust air stream.
(f) Provide an airflow switch to detect interruption in airflow with
audible and visible alarms, local as well as at the Engineering Central
Center.
4.6 REAGENT GRADE WATER TREATMENT ROOMS
4.6.1 GENERAL
These rooms, generally located near Supply-Processing and Distribution
(SPD) or Laboratories, contain equipment that produces de-ionized
water. The room should be well ventilated because of corrosive
chemicals used in the process to produce deionized water.
4.6.2 EXHAUST AIR SYSTEMS
The exhaust system shall have the following specific features:
(a) Maintain a minimum of exhaust at the rate of 8 air changes per
hour.
(b) Exhaust fan shall be on emergency power.
(c) The exhaust systems shall have corrosion-resistant all welded
stainless steel ductwork spark-proof construction fans and explosion
proof motors.
HVAC DESIGN MANUAL
4-2
HVAC REQUIREMENTS FOR UNOCCUPIED AREAS