Draft 7-6-95
Design Standards
Radiology - Storage, Unexposed Film & Chemicals
ARCHITECTURAL
CONDITIONING
Ceiling:
--
Ceiling Ht:
--
Dry Bulb Temp Cooling:
25C (78F)
Wall Finish:
--
22C (72F)
Wainscot:
--
Minimum % Outside Air:
100%
Base:
--
Yes
Floor Finish:
--
Noise Criteria:
NC-40
Slab Depr:
--
Steam:
--
Notes:
Relative Humidity/Cooling:
50%
Relative Humidity/Heating:
30%
SPECIAL EQUIPMENT
Minimum Air Changes/Hr.:
4
Room Pressure:
Negative
None
AC Load-Equipment:
None
LIGHTING
AC Load-Lighting:
(1.3w/sf)
Number of People:
0
General:
--
--
Special:
--
Notes:
1. Maintain negative pressure
Notes:
by exhausting.
POWER
2. 15% more air than supply
General:
--
PLUMBING AND MEDICAL GASES
Emergency:
--
Notes:
--
Cold Water:
--
Hot Water:
--
COMMUNICATION
Laboratory Air:
--
Laboratory Vacuum:
--
ADP:
--
Sanitary Drain:
--
Radio:
--
Reagent Grade Water:
--
Telephone:
--
Medical Air:
--
Intercom:
--
Medical Vacuum:
--
Pub. Addr:
--
Oxygen:
--
Notes:
Notes:
VA Design Guide
Community Based Outpatient Clinic
PAGE 6 - 7