Draft 7-6-95
Design Standards
General Laboratory
ARCHITECTURAL
CONDITIONING
Ceiling:
GWB
Ceiling Ht:
2400 mm (8'-0")
Dry Bulb Temp Cooling:
24C (76F)
Wall Finish:
GWB
22C (72F)
Wainscot:
--
Minimum % Outside Air:
100%
Base:
4" Resilient Base
Yes
Floor Finish:
Noise Criteria:
NC-45
Slab Depr:
--
Steam:
--
Notes:
Relative Humidity/Cooling:
50%
Relative Humidity/Heating:
30%
SPECIAL EQUIPMENT
Minimum Air Changes/Hr.:
12 (SA)
Room Pressure:
Negative
None
AC Load-Equipment:
(3.9w/sf)
LIGHTING
AC Load-Lighting:
(3.0w/sf)
Number of People:
5
General:
(70fc)
--
Special:
--
Notes:
--
Notes:
POWER
PLUMBING AND MEDICAL GASES
General:
Cold Water:
Yes
Emergency:
2000 w - 208 V
Hot Water:
Yes
Special:
Laboratory Air:
--
Notes:
--
Laboratory Vacuum:
--
Sanitary Drain:
Yes
COMMUNICATION
Reagent Grade Water:
--
Medical Air:
--
ADP:
--
Medical Vacuum:
--
Radio:
--
Oxygen:
--
Telephone:
Yes
Notes:
Intercom:
--
Pub. Addr:
--
Notes:
VA Design Guide
PAGE 6 - 1
Community Based Outpatient Clinic