Draft 7-6-95
Design Standards
Office/Examination Room
ARCHITECTURAL
CONDITIONING
Ceiling:
Ceiling Ht:
2400 mm (8'-0") (see note 1)
Dry Bulb Temp Cooling:
25C (78F)
Wall Finish:
GWB
22C (72F)
Wainscot:
--
Minimum % Outside Air:
15%
Base:
4" Resilient Base
--
Floor Finish:
Noise Criteria:
NC-40
Sound Protection:
Yes (see note 2)
Steam:
--
Slab Depr:
--
Relative Humidity/Cooling:
50%
Notes: 1. Perimeter partitions full height
Relative Humidity/Heating:
30%
Minimum Air Changes/Hr.:
4
Room Pressure:
0
SPECIAL EQUIPMENT
AC Load-Equipment:
2.9 W/SF
AC Load-Lighting:
2.0 W/SF
None
Number of People:
2
LIGHTING
--
Notes:
--
General:
70FC-3.5W/SF
Special:
--
PLUMBING AND MEDICAL GASES
Notes:
Cold Water:
Yes
POWER
Hot Water:
Yes
Laboratory Air:
--
General:
1200 W
Laboratory Vacuum:
--
Emergency:
--
Sanitary Drain:
Yes
Notes:
--
Reagent Grade Water:
--
COMMUNICATION
Medical Air:
--
Medical Vacuum:
--
ADP:
Empty Conduit
Oxygen:
--
Radio:
--
Notes:
Telephone:
Yes
Intercom:
--
Pub. Addr:
--
Nurse Call:
Yes
Notes:
VA Design Guide
PAGE 5 - 5
Community Based Outpatient Clinic