Draft 7-6-95
Design Standards
Reception
ARCHITECTURAL
CONDITIONING
Ceiling:
Ceiling Ht:
2400 mm (8'-0")
Dry Bulb Temp Cooling:
25C (78F)
Wall Finish:
Wainscot:
22C (72F)
Base:
4" RB
Minimum % Outside Air:
15%
Floor Finish:
Carpet
--
Slab Depr:
Noise Criteria:
NC-40
Notes:
Steam:
--
Relative Humidity/Cooling:
50%
SPECIAL EQUIPMENT
Relative Humidity/Heating:
30%
Minimum Air Changes/Hr.:
6
None
Room Pressure:
--
LIGHTING
AC Load Lights:
2.0W/SF
AC Load Equipment:
2.4W/SF
General:
(See notes 1 and 2)
Number of People:
18
Special:
--
Emergency
Notes:
1. 50FC - 2.5 W/SF; 3 LAMP
PLUMBING AND MEDICAL GASES
FIXT=160W
2. 20FC - 1.0W/SF; 2 LAMP
Cold Water:
--
FIXT=100W
Hot Water:
--
Laboratory Air:
--
POWER
Laboratory Vacuum:
--
Sanitary Drain:
--
General:
--
Medical Air:
--
Special:
--
Medical Vacuum:
--
Emergency:
--
Oxygen:
--
--
--
Anesthesia Evac:
--
Patirnt Monitor:
--
Other:
--
Nurse Call:
--
Code One:
--
CCTV:
--
Telephone:
Yes
Intercom:
Yes
Pub. Addr:
Yes
ADP:
--
Radio:
--
VA Design Guide
Community Based Outpatient Clinic
PAGE 4-1