Design Standards
Multipurpose Examination Room
ARCHITECTURAL
CONDITIONING
Ceiling:
Gypsum wallboard lay-in ceiling
panels
Dry Bulb Temp Cooling:
25C (78F)
Ceiling Ht:
2700 mm (9'-0")
22C (72F)
Wall Finish:
Paint
Minimum % Outside Air:
25
Wainscot:
--
--
Base:
Resilient base
Noise Criteria:
NC-40
Steam:
--
Slab Depr:
--
Relative Humidity/Cooling:
50%
Notes:
1. Provide STC partitions and
Relative Humidity/Heating:
30%
doors
Minimum Air Changes/Hr.:
4
2. 900 mm (3'-0") wide door
Room Pressure:
0
2
AC Load Lighting:
30 W/m (2.8 W/sf)
65 W/m 2 (6W/sf)
SPECIAL EQUIPMENT
AC Load-Equipment:
Number of People:
3
None
--
Notes:
LIGHTING
General:
50 FC ambient/100 FC task
PLUMBING AND MEDICAL GASES
Special:
--
Notes:
1. Dual-level switching provided
Cold Water:
Yes
50/10 FC levels.
Hot Water:
Yes
2. 600 mm X 1200 mm (2'x4')
Laboratory Air:
--
Laboratory Vacuum:
--
fixture, acrylic prismatic lens,
Sanitary Drain:
Yes
W/4-F32T8 lamps, 3500K,
Reagent Grade Water:
--
Medical Air:
--
CRI=75 (Minimum)
Medical Vacuum:
--
Oxygen:
--
POWER
Notes:
General:
Emergency:
--
Notes:
COMMUNICATION
ADP:
Yes
Radio:
--
Telephone:
Yes
Intercom:
--
Pub. Addr:
--
Notes:
VA DESIGN GUIDE
AMBULATORY CARE (Hospital Based)
PAGE 6-1