FINAL DRAFT 10-31-95
REVISED January 1997
Design Standards
Toilet/Bath Wheelchair
ARCHITECTURAL
Ceiling:
Gypsum Wallboard, paint
CONDITIONING
Ceiling Ht:
2700 mm (9'-0")
Dry Bulb Temp Cooling:
25C (78F)
Wall Finish:
Paint
25C (78F)
Wainscot:
Ceramic Tile
Minimum % Outside Air:
--
Base:
Ceramic tile
Yes
Floor Finish: Ceramic tile
Noise Criteria:
NC-40
Slab Depr:
75 mm (3") depression to allow
Steam:
--
entire floor area to slope to
Relative Humidity/Cooling:
--
drain
Relative Humidity/Heating:
--
Notes:
1. 1120 mm (3'-8") wide door
Minimum Air Changes/Hr.:
Room Pressure:
Negative
SPECIAL EQUIPMENT
2
AC Load Lighting:
15 W/m (1.4 Wsf)
None
AC Load-Equipment:
---
Number of People:
1
LIGHTING
Special Exhaust:
--
General:
30 FC
Notes:
Special:
--
PLUMBING AND MEDICAL GASES
Notes:
1. 600 mm x 1200 mm (2'x4')
Cold Water:
Yes
Hot Water:
Yes
fixture, acrylic prismatic lens,
Laboratory Air:
--
W/2-F32T8 lamps, 3500K,
Laboratory Vacuum:
--
CRI=75 (Minimum), UL listed
Sanitary Drain:
Yes
for wet locations.
Reagent Grade Water:
--
Medical Air:
--
POWER
Medical Vacuum:
--
General:
--
Oxygen:
--
Emergency:
--
Notes:
Notes:
COMMUNICATION
ADP:
--
Radio:
--
Telephone:
--
Intercom:
--
Pub. Addr:
--
Notes:
1. Nurse Call
VA DESIGN GUIDE
AMBULATORY CARE (Hospital Based)
PAGE 5-4