FINAL DRAFT- 10/31/95
REVISED January 1997
Design Standards
Vital Sign Station
ARCHITECTURAL
CONDITIONING
Ceiling:
Ceiling Ht:
2700 mm (9'-0")
Dry Bulb Temp Cooling:
25C (78F)
Wall Finish:
Paint
22C (72F)
Wainscot:
--
Minimum % Outside Air:
15
Base:
Resilient base
--
Floor Finish:
Noise Criteria:
NC-35
Slab Depr:
--
Steam:
--
Notes:
Relative Humidity/Cooling:
50%
Relative Humidity/Heating:
30%
SPECIAL EQUIPMENT
Minimum Air Changes/Hr.:
4
Room Pressure:
0
None
2
AC Load Lighting
17 W/m (1.6 W/sf)
35 W/m 2 (3.2W/sf)
AC Load Equipment:
LIGHTING
Number of People:
4
General:
50 FC
--
Special:
--
Notes:
Notes:
1.
Switching per station
2.
600 mm x 1200 mm (2'x4')
PLUMBING AND MEDICAL GASES
Cold Water:
Yes
fixture, acrylic prismatic lens,
Hot Water:
Yes
with 2-F32T8 lamps 3500K,
Laboratory Air:
--
CRI=75 (Minimum)
Laboratory Vacuum:
--
Sanitary Drain:
Yes
POWER
Reagent Grade Water:
--
General:
Medical Air:
--
Emergency:
--
Medical Vacuum:
--
Notes:
Oxygen:
--
Notes:
ADP:
Yes
Radio:
--
Telephone:
Yes
Intercom:
--
Pub. Addr:
--
Notes:
VA DESIGN GUIDE
AMBULATORY CARE (Hospital Based)
PAGE 4-1