ELECTRIC MOTOR MAINT ENANCE
ISSUE:
BACKGROUND:
In response to inquiries from several VAMCs concerning greasing of motor
bearings, following information is provided as guidance:
RECOMMENDATIONS:
1. Follow motor manufacturer's recommendations on lubrication.
2. In the absence of manufacturer's instructions, the following *table is a guide for
Type of
Up to 7.5 HP
10-40 HP
50-100HP
Over 100 HP
service
Easy
10Yr
7Yr
4Yr
1Yr
Standard
7Yr
4Yr
1.5Yr
6Mo
Severe
4Yr
1.5Yr
9Mo
3Mo
Very Severe
9Mo
4Mo
3Mo
2Mo
* Table based on recommendations published in `Energy User News', Feb. 1998.
Terminology:
Easy Service: The equipment is used about one hour per day, such as valves,
door openers, tools etc.
Standard Service: The equipment is used one to two shifts per day, such as
Severe Service: The equipment is used on three shifts for seven days, such as
fans, and pumps (HVAC equipment in hospitals).
Very Severe Service: The equipment is used in dirty vibrating applications,
pumping hot fluids or air or in high ambient environment.
2 March 1998
FM-187C-DA85