Design Standards
Ambulatory Surgery Operating Room (Topical Anesthesia)
ARCHITECTURAL
CONDITIONING
Ceiling:
Gypsum Wall Bd SC
Dry Bulb Temp Cooling:
25C( 78F)
Ceiling Ht:
2900 mm (9'-6")*
22C(72F)
Wall Finish:
SC
Minimum % Outside Air:
100
Wainscot:
--
Yes
Base:
Resilient sheet flooring intergral base
Noise Criteria:
NC-40
Floor Finish:
Resilient sheet flooring
Steam:
--
Slab Depr:
--
Relative Humidity/Cooling:
50%
Notes:
--
Relative Humidity/Heating:
30%
SPECIAL EQUIPMENT
Minimum Air Changes/Hr.:
6
None
Room Pressure:
SA + 15%
AC Load Lights:
--
LIGHTING
AC Load Equipment:1
--
General:
100 FC
Number of People:
3
Special:
Portable examining light
--
Notes:
1. 600mm x 1200mm (2'x4')
PLUMBING AND MEDICAL GASES
Cold Water:
Yes
acrylic prismatic lens, W/3-F32T8
Hot Water:
Yes
lamps, 4100K CRI=85 (Minimum)
Laboratory Air:
--
POWER
Laboratory Vacuum:
--
General:
Sanitary Drain:
Yes
Special:
--
Reagent Grade Water:
--
Emergency:
--
Medical Air:
Yes
Medical Vacuum:
Yes
Oxygen:
Yes
ADP:
Yes
Radio:
--
Telephone:
Yes
Intercom:
--
Pub. Addr:
Empty Conduit
VA DESIGN GUIDE
AMBULATORY CARE INVASIVE PROCEDURES SUITE
PAGE 4-2